Building Technologies Basic documentation: Communication via the KNX bus CE1P3127en
HVAC Products Communication via zone addresses 30.08.2007
7.3.2 RXB/RXL room controllers
In ACS Service Applications > Parameter settings , open the menu tree of the
RXB/RXL room controller for which the zone address is to be set.
Double-click the menu line "Communication" to open the operating page, and
select the zone for which the address is to be set. Double-click to open the
dialog box for entry of the address.
Enter the zone address and click OK to confirm the value entered.
7.3.3 Zone addressing with the QAX34.3 room unit
With the RXB/RXL room controllers, the zone addresses can also be set with the
QAX34.3 room unit (Minor parameterization, see section 5.6.1).
P008 Geographical zone (apartment) 1…126 -1 = Default value
P009 Geographical zone (room) 0…63 1 = Default value
P010 Geographical zone (subzone) 0…15 1 = Default value
P011 Time-switch zone (apartment) 1…126 1 = Default value
P012 Time-switch zone (room) 0…63 1 = Default value
P013 Time-switch zone (subzone) 0…15 1 = Default value
P014 Heat distribution zone, air heater 1…31 -1 = Default value
P015 Refrig distrib. zone, cooling coil 1…31 -1 = Default value
P016 Heat distr zone heating surface. 1…31 -1 = Default value
P017 Refrig distr zone cooling surface 1…31 -1 = Default value
P018 Outside temperature zone 1…31 1 = Default value
P023 Master/slave zone (group) 1…126 1 = Default value
P023 Master/slave zone (room) 0…63 -1 = Default value
P024 Master/slave zone (subzone) 0…15 1 = Default value
"P008" indicates that the "Geographical zone (apartment)" in the RXB/RXL room
controllers is parameter no. 008. For more information, refer to document
CM110385.
For the RM… controllers, the default value in the QAX34.3 room unit is "-1" rather
than "----". Both default values indicate that the zone is "out of service" and that no
process values are transmitted within the zone.
Minor parameterization
Parameter numbers and
associated zones
Notes