Building Technologies Basic documentation: Communication via the KNX bus CE1P3127en
HVAC Products Device addresses via ACS 30.08.2007
5.6.1 RXB/RXL device address with QAX34.3 room unit
The QAX34.3 room unit covers all the standard room unit functions. The room unit
can also be used to set the RXB/RXL room controller parameters via PPS2.
The QAX34.3 room unit is not suitable for direct connection to the KNX bus.
The tool socket (RJ45) on the RXB/RXL room controllers serves as a PPS2
interface and a bus interface (CE+ und CE-). This tool socket can be used to
connect room units (PPS2), the OCI700 service interface or the RMZ792 bus
operator unit.
Physical address (network address)
Zones (for communication in LTE mode)
Setpoints
Master/slave settings
All parameters (refer to the detailed in formation in document CM110385)
Group addresses (bindings) cannot be assigned. This must be carried out with the
ETS.
Function of the buttons
10385Z70
+ = Count/move upward
= Count/move downward
> = Esc (exit without confirmation)
< = Enter (confirm/acknowledge)
Restart
After significant parameter changes, the room
controller is restarted
"Minor parameter setting", with access in parameter mode is sufficient for setting
the device address or complete network address:
Hold down the < , > and buttons simultaneously for approximately 2 s until the
display turns dark (no values displayed).
Then briefly press the button twice in succession.
The display now reads
0 (mode 0).
The following modes can be selected with the +/– buttons:
0 = Normal mode (normal room unit functions).
2 = Display mode:
The parameter display is prefaced with the letter "d", e.g. d 15.
Use +/– to find the required number and acknowledge with < (Enter).
The relevant value is then displayed.
Press < (Enter) or > (Esc) to return to the list.
3 = Parameter mode
Start the parameter mode by pressing < (Enter), enabling the parameter
numbers to be selected and the parameter values to be set. Parameter
numbers are preceded by the letter "P", e.g. P 2.
Notes
Parameter setting
Minor parameter setting
Major parameter setting
Note
Minor parameter setting