Building Technologies Basic documentation: Communication via the KNX bus CE1P3127en
HVAC Products Device addresses via ACS 30.08.2007
3 = Parameter mode (continued)
Press +/– to find a new parameter number and confirm with < (Enter). The
value concerned is then displayed.
Press +/– to change the value and confirm with < (Enter).
Press > (Esc) to return to the parameter number level without making any
changes.
Press > (Esc) again for access to the list mode and a third time for access
to the normal (room unit) mode.
The device address or network address is set via the following parameter numbers:
P 1 Area )
P 2 Line )> Network address
P 3 Device address )
The same applies to the RXB/RXL room controllers as to the Synco bus devices,
i.e. the area and line address is adopted by the super-ordinate area/line couplers.
When setting the area/line address via the room unit, take care not to reprogram
any valid addresses.
Modifiable parameters
in parameter mode
Notes