74/120
Building Technologies Basic documentation: Communication via the KNX bus CE1P3127en
HVAC Products Communication via zone addresses 30.08.2007
7.3 Addressing the zones with ACS
7.3.1 RM… controllers
For the RXB/RXL room controllers and the QAW740 room unit, the zone addresses
can also be set via ACS Service.
The use of ACS Service to set the zone addresses is particularly efficient for
extensive networks.
Once the relevant device has been selected, the menu tree has the same structure
as the path sequence for the operator units:
Commissioning > Communication > Room
1. In ACS Service Applications > Parameter settings , open the menu tree of the
controller for which the zone address is to be set.
2. Double-click the menu line "Room" to open the operating page, and select the
zone for which the address is to be set. Double-click to open the dialog box for
your input.
3. Enter the zone address and click OK to confirm the value entered.
Introduction