Building Technologies Basic documentation: Communication via the KNX bus CE1P3127en
HVAC Products Device addresses via ACS 30.08.2007
5.1.3 Establishing a connection
If "Refresh device list?" is answered with "Yes", the connection is established
automatically, the device list is read and the reference data points are refreshed in
the devices.
Update the device list with Yes
Communication: Connected
5.1.4 Edit device list
The following shows how to set a device address via ACS Service. It is assumed
that the user is familiar with ACS and how to use it.
In ACS Service select Plant > Edit device list… to open the "Edit device list" dialog box.
If the connection status is not already [State - Connected] , connection is established
automatically before the "Edit device list" dialog box is opened (see next page).