Building Technologies Basic documentation: Communication via the KNX bus CE1P3127en
HVAC Products Commissioning notes 30.08.2007
Select "Off" on the "Preselection" line and confirm by pressing the OK knob.
Press ESC to return to the "Main menu" page.
Select "Commissioning" and press the knob.
Before the "Commissioning" page is displayed, the following warning appears:
Confirm the display of OK by pressing the knob (this causes the plant to stop). The
"Commissioning" page now appears.
Select the "Communication" line for example, by rotating the knob, and then press
the knob to open the "Communication" page.
Main menu > Commissioning > Communication
Press the knob for access to the "Basic settings" page
Plant operation = Off
A
ction
Return to main menu
A
ction
Plant stopping
A
ction
A
ction
Communication
A
ction
Commissioning
Basic configuration...
Extra configuration...
Settings...
Communication...
Communication
Basic settings...
Room...
Holidays//Special days...
Distribution zones...
Caution!
Plant stops
ESC OK
Plant operation
Preselection: Off
State: Off
Cause: Plant op. selector
Main menu
Commissioning...
Time switch...
Room operating mode...
Plant operation...