e1973c-4
02.2004
23
Fire & Security Products
Siemens Building Technologies Group
Zone isolation procedure
1. Press
St
.
Display shows
2. Select option 2. 1. 1.
Display shows
Now you can disable single zones, a range of
detector zones or all zones as described be-
low:
Disable single zones
1. Enter the desired zone number (e. g.
2).
Display shows
2. Press
ok
to disable the single zone.
Display shows
3. Enter 99 for permanent disabling.
Display shows
or
"
Enter the desired disabling time in full
hours (e. g. 2).
Display shows
4. Press
St
to finish the zone disabling
procedure.
or
"
Enter another single zone number to disable.
Display shows
The yellow LED isolation is on.
Disable a range of zones
1. Enter the first zone number of the
range of zones to be disabled (e. g. 2).
Display shows
2. Enter the last zone number of the range
of zones to be disabled (e. g. 5).
Display shows
3. Enter 99 for permanent disabling.
Display shows
or
"
Enter the desired disabling time in full
hours (e. g. 2).
Display shows
4. Press
St
to finish the zone disabling
procedure.
or
"
Enter another zone number to disable.
Display shows
The yellow LED isolation is on.
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
DISable zones: (range ### to ###)
> zone no.? (555 = all)
hm: back to menu Stop: end operating
zone ### SELECTED. ok = SINGLE zone
> 2nd zone no.? (range ### − ###)
hm: back to menu Stop: end operating
zone ### SELECTED
> hours DISABLED? (99=permanent)
Permanent disabling
zone ### permanent DISABLED
(hm = end) new zone no.?
hm: back to menu Stop: end operating
Disabling for a few
hours
zone ### DISABLED for ## hours
(hm = end) new zone no.?
hm: back to menu Stop: end operating
parts of system DISABLED total:###
WED
21.7.00 15:00
zone ### SELECTED. ok = SINGLE zone
> 2nd zone no.? (range ### − ###) _
hm: back to menu Stop: end operating
zone ### − ### SELECTED
> hours DISABLED? (99=permanent)
hm: back to menu Stop: end operating
Permanent disabling
zones ### − ### permanent DISABLED
(hm = end) new zone no.?
hm: back to menu Stop: end operating
Disabling for a few
hours
zones ### − ### DISABLED for ## hours
(hm = end) new zone no.?
hm: back to menu Stop: end operating
parts of system DISABLED total:###
WED
21.7.00 15:00