49
8.4 Checks
8.4.1 Checking the flue
Check that the flue is undamaged and complete.
8.4.2 Checking the expansion vessel pressure
It is recommended that the expansion vessel on the water side
is drained and that the prefilling pressure is not less than
1
bar
. If this is not the case, pressurize it to the correct value
(see section "Expansion vessel").
Once the checks described above have been completed:
– refill the boiler as described in section "SYSTEM Filling"
– check that the siphon has been filled correctly
– Start the boiler, activate the "Chimney sweep function" and
carry out combustion analysis as detailed in Appendix 2
– refit the front panel securing it with the two screws which
were removed previously.
8.5 Circuit Board Replacement
Type No. Description
Setting for
GIULIA
SYSTEM
25
tS 0.1
Index showing boiler power
in kW
0 = 25 (METHANE)
2 = 25 (GPL)
0
tS 0.2
0 = combi
1 = storage tank with
thermostat or heating only
2 = N/A
3 = N/A
4=instant with solar power
input
5 = open vent
6 = KIT HYBRID instant boiler
7 = Edea Hybrid
8 = Edea Hybrid SPAIN
CENTRALIZED
9 = HYBRIDWALL istant boiler
10 = HYBRIDWALL hot water
tank boiler
1
To enter "Parameter setting and display" refer to the indica-
tions provided in the specific section.
If the
gas valve
are replaced, the user must still carry out the
entire phase of "Chimney sweep function" described in the
specific section.
8.6 Malfunction codes and possible solutions
LIST OF MALFUNCTION/FAULT ALARMS
Type No. Fault Solution
AL 02
Low water pressure in
system
- Restore pressure
- Check for any leaks in the
system
AL 03
High water pressure in
system
- Empty the system via
the drain valve on the
hydraulic assembly and
bring the pressure to
approximately 1.2 bar
AL 04
Domestic hot water
sensor fault (return
sensor fault for T
models)
- Check connections
- Check the sensor is
working
AL 05 Delivery sensor fault
- Check connections
- Check the sensor is
working
AL 06 No flame detection
- Check the integrity of the
electrode and check that it
is not grounded
- Check gas availability and
pressure
- Check the operation of the
gas valve
AL 07
Safety thermostat
intervention
- Check the sensor or
thermostat connections
- Deaerate the system
- Check the bleed valve
- Replace the sensor or the
thermostat
- Check that the pump
impeller is not blocked
AL 08
Fault in the flame
detection circuit
- Check the integrity of the
electrode and check that it
is not grounded
- Check the operation of the
gas valve
AL 09
No water circulating in
the system
- Check the rotation of the
pump rotor
- Check the electrical
connections
- Replace the pump
AL 11
Gas valve modulator
disconnected
- Check the electrical
connection
AL 12
Domestic hot water
sensor fault in tank
mode
- Set the parameter tS 0.4
(Combustion configuration)
to 0
AL 13
Exhaust sensor
intervention
- Check the sensor is
working
- Replace the smoke probe
AL 14 Exhaust sensor fault
- Replace the smoke probe
- Check the electrical
connection of the smoke
probe
- Contact the Technical
Assistance Centre
AL 15
Fan check cable
disconnected
- Check the connection
cable between the fan and
the board
AL 28
Maximum number of
consecutive resets
reached (6)
- Wait 1 hour and try
unblocking the board again
- Contact the Technical
Assistance Centre
AL 30
Return sensor fault
(boiler sensor fault for
T models)
- Replace the return probe
- Check parameters
- Contact the Technical
Assistance Centre
AL 37
Fault due to low
network voltage
- Check the voltage
- Contact your network
provider