DL100 Series Universal Low-Power Inverter
42 Detailed Description of Functions
set by the multi-speed control parameter function code group ([F5.01] ~ [F5.07]).
4 Forward jog control
5 Reverse jog control
When the run command channel selection external terminal is valid, this parameter
defines the input terminal of the external jog signal.
6 Frequency setting channel selection 1
7 Frequency setting channel selection 2
When the frequency input channel is the external terminal selection (F0.00=4),
the frequency setting channel of the inverter is determined by the state of the two
terminals. For the corresponding relationship, refer to the relevant description of
the [F0.00] parameter.
8 Free stop control
Close the terminal corresponding to this parameter, the inverter will block the
output.
9 Three-wire operation control
When the three-wire mode is selected as the running command terminal
combination mode, the external terminal defined by this parameter is the inverter
stop trigger switch. For the three-wire control mode, refer to the detailed
description of the function code [F0.06].
10 DC brake control
When the inverter is stopped, if the terminal defined by this parameter is closed,
when the output frequency is lower than the initial frequency of DC braking, the
DC braking function will be activated until the terminal is disconnected. Refer to
the description of [F1.05] ~[F1.07] for the relevant parameters of DC braking.
11 Forward control
12 Reverse control
13 Fault reset
When the inverter is in a fault state, closing the terminal set by this parameter
can clear the inverter fault.
14Reserve
15Reserve
16External fault input
When the terminal set by this parameter is closed, it indicates that the external
equipment has a fault. At this time, for the safety of the equipment, the inverter
will block the output and display the external fault signal Fu.16 at the same time.
17Disconnection input
When the terminal set by this parameter is closed, it indicates that the external
equipment has a disconnection fault. At this time, for the safety of the equipment,
the inverter will block the output and display the external fault signal Fu.17 at the