DL100 Series Universal Low-Power Inverter
Detailed Description of Functions 51
6.6 Multi-speed section and PLC operating parameter group
Basic characteristic setting of multi-speed operation (decimal setting).
LED units: simple PLC action selection
0: Simple PLC is invalid
1: Simple PLC effective
2: Simple PLC conditions are valid
When the LED ones place is 1 (PLC is valid), after the inverter is started, the
inverter enters the simple PLC running state when the priority of the frequency
channel is allowed.
When LED ones place selection 2 (PLC condition is valid), when the external
PLC input terminal is valid (PLC input terminal is selected by parameter [F3.01] ~
[F3.04]), the inverter runs in simple PLC mode; external input terminal When it is
invalid, the inverter automatically enters the frequency setting mode with lower
priority.
LED ten digits: Simple PLC operation mode selection
0:Single loop mode
The inverter first runs at the set frequency of the first speed, and outputs the
frequency step by step according to the set running time. If the set running time of
a certain speed is 0, the speed will be skipped, and the inverter will stop output
after running for one cycle. It is necessary to input a valid running command again
to start the next cycle.
1: Single cycle shutdown mode
The basic operation mode is the same as mode 0. The difference is that after the
inverter runs for a certain speed, it first reduces the output frequency to 0
according to the specified deceleration time, and then outputs the next frequency.
2: Keep final value mode
The basic operation mode is the same as that of mode 0, the inverter will not
stop after running a single cycle, and run at a stage speed that is not zero at the last
time. The other processes are the same as mode 1.
3: Keep set value mode
The basic operation mode is the same as that of mode 0, the inverter will not
stop after running a single cycle, and run at a stage speed that is not zero at the last
time. The other processes are the same as mode 1.
4: Continuous loop mode
The basic operation mode is the same as that of mode 0. After one cycle of
F5.00 Multi-speed operation mode Predetermined area
:
0000~0042H