trouble LED. The event must be acknowledged by pressing ACK to silence the piezo. If discharge continues further, and the batteries reach
the depleted state, the sounder activates and the trouble LED flashes again.
If the system is running from battery backup, AC has failed, and the batteries are depleted, one of the two following scenarios occurs:
• The system will not initiate a first alarm on Aux Relays, NACs or RACs after reaching depleted battery. In this case, if an alarm precedes
the depleted battery state, the system continues to function. This is the default. Alarms are indicated at the User Interface.
• The system shuts down 60 seconds after indicating the depleted state. This feature is necessary for Canada (S527). To activate this
choice, a jumper must be clipped out. Refer to Connecting the field wiring and AC power for information on enabling this option.
3.3.4 Environmental
Temperature. This equipment operates normally within the temperature range of 0° C (32° F) to 49° C (120° F), inclusive.
Humidity. This equipment operates normally under non-condensing humidity conditions up to 93% relative humidity @ 32° C (90° F).
3.3.5 Listings and approvals
This equipment meets the requirements of the following agencies:
• UL (UL 864)
• ULC (S527)
• FM (Class No. 3010)
3.3.6 Codes and standards
If the 4004R is installed in accordance with either NFPA 12A or NFPA 2001, the system must employ an additional mechanically-operated
manual release mechanism. The installer should be familiar with the relevant codes listed below, as well as any other applicable local codes
and standards, when installing a fire alarm system.
• NFPA 72 National Fire Alarm Code and Signaling Code.
• NFPA 11 Standard for Low-Expansion Foam and Combined Agent Systems.
• NFPA 11A Standard for Medium- and High-Expansion Foam Systems.
• NFPA 12 Standard for Carbon Dioxide Extinguishing Systems.
• NFPA 12A Standard on Halon 1301 Fire Extinguishing Systems.
• NFPA 13 Standard for Installation of Sprinkler Systems.
• NFPA 14 Standard for the Installation of Standpipe and Hose Systems.
• NFPA 15 Standard for Water Spray Fixed Systems for Fire Protection.
• NFPA 16 Standard for the Installation of Deluge Foam-Water Sprinkler and Foam-Water Spray Systems.
• NFPA 16A Standard for the Installation of Closed-Head Foam-Water Sprinkler Systems.
• NFPA 17 Standard for Dry Chemical Extinguishing Systems.
• NFPA 17A Standard for Wet Chemical Extinguishing Systems.
• NFPA 25 Standard for Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems.
• NFPA 70 National Electric Code.
• NFPA 72 National Fire Alarm Code and Signaling Code.
• NFPA 101 Life Safety Code.
• NFPA 750 Standard on Water Mist Fire Protection Systems.
• NFPA 2001 Standard on Clean Agent Fire Protection Systems.
• ULC S524 Standard for Installation of Fire Alarm Systems (Canadian Systems).
page 12 579-354 Rev. X
4004R Fire Alarm installation, programming, and operating instructions