EasyManua.ls Logo

Simplex 4004R - Wiring Shared Abort;Manual Release with an Internal Current Limiting Resistor

Simplex 4004R
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 18: SPM field wiring connections Note:
Connect abort switches and manual release stations
as shown in the figure. When using external current-
limiting resistors, the special purpose monitoring
circuits cannot be wired Style D and must only be
wired Class B.
The series current-limiting resistor shall be terminated
and enclosed inside the mounting box of the first
abort switch.
5.3.3 Wiring shared Abort/Manual Release with an internal current limiting resistor
Adhere to Figure 19 and the following guidelines when wiring SPM circuits with internally current-limited abort switches;
The + connection from the SPM is made to the lead of the factory-installed, current limiting resistor. As shown in Figure 19, the –
connection is made to the open terminal. The terminal that is connected to the current limiting resistor must not be tampered with.
Use only manual release and abort switches that are UL Listed for fire use.
Connect the manual release switch between the last abort switch and the end-of-line resistor. See Figure 20.
Use only UL Listed abort switches that are listed with an internal resistance of 1.2 K Ohms.
No more than five abort switches are to be connected to the same circuit.
All wiring must be 12 AWG maximum to 18 AWG minimum.
Conductors must test free of all grounds.
All wiring is supervised and power limited.
Leave 3.3 K, 1/2 W (378-115) resistor across all unused SPM terminals. See item 4 in Figure 20.
Terminate Style B (Class B) circuits with a listed 3.3K, 1W (Simplex Part Number 733-893) end-of-line resistor. See item 5 in Figure 20.
For Canadian applications, use ULC-listed end-of-line resistors 2081-9010C, 2081-9018, or 2081-9037C.
Terminate Style D (Class A) circuits with a listed 3.3K, 1 W (Simplex Part Number 733-893) end-of-line resistor. See item 6 in Figure 20.
Maximum line resistance is 50 Ohms.
Normal condition (no devices closed). Current at 24 VDC: 6.0 mA
Manual Release condition. Current at 24 VDC: 25 mA
SPM circuits do not support the connection of smoke or heat detectors.
When SPM wiring is routed outside the building, use Listed Secondary Protector 2081-9044 or 2081-9028. A protector must be
installed at the building entrance such that protected wiring is segregated from unprotected (outdoor) wiring.
page 26 579-354 Rev. X
4004R Fire Alarm installation, programming, and operating instructions

Table of Contents

Related product manuals