Figure 17: Dedicated Class A/B SPM circuits
5.3.2 Wiring shared Abort/Manual Release with an external resistor
Adhere to Figure 18 and the following guidelines when wiring SPM circuits with an external current-limiting resistor:
Use only manual release and abort switches that are UL Listed for fire use.
To ensure that a manual release switch causes a short condition and not a current-limited condition, connect the manual release switch
between the first abort switch and the 4004R. See Figure 18, item 8.
Both manual release stations and abort switches must be normally open.
All wiring must be 12 AWG maximum to 18 AWG minimum.
Conductors must test free of all grounds.
All wiring is supervised and power limited.
Leave 3.3 K, 1/2 W (378-115) resistor across all unused SPM terminals. See item 4 in Figure 18.
Terminate Style B (Class B) circuits with a listed 3.3K, 1W (Simplex Part Number 733-893) end-of-line resistor.
For Canadian applications, use ULC-listed end-of-line resistors 2081-9010C, 2081-9018, or 2081-9037C.
Terminate Style D (Class A) circuits with a listed 3.3K, 1 W (Simplex Part Number 733-893) end-of-line resistor.
Maximum line resistance is 50 Ohms.
Normal condition (no devices closed). Current at 24 VDC: 6.0 mA
Manual Release condition. Current at 24 VDC: 25 mA
SPM Circuits do not support the connection of smoke or heat detectors.
When SPM wiring is routed outside the building, use Listed Secondary Protector 2081-9044 or 2081-9028. A protector must be
installed at the building entrance such that protected wiring is segregated from unprotected (outdoor) wiring.