Table 11: Programming Manual Release Time Delay
Method Description
Text-based
programming
The sixth prompt, shown below, asks you to set the Manual Release Delay Timer.
[06] MANUAL RELEASE TIMER:
1 = Immediate (no delay)
*2 = 5 sec.
d 3 = 10 sec.
4 = 15 sec.
5 = 20 sec.
6 = 25 sec.
7 = 30 sec.
(d=default, *=current setting)
Select Number(X=exit):
Enter the number corresponding to the value you want to select and press the carriage return.
Front panel
programming
Seven selections are available – ranging from 0 to 30 seconds, selectable in five-second intervals. Use the RESET
key to scroll through the selections. When the desired choice is illuminated, press the ACK key to save the
selection in memory and move to the next programming step.
6.9 Programming Abort Switch Operation
The Abort Release Time Delay specifies the action that occurs when the abort switch is released. This option applies only to Agent Release
applications.
Note: For all choices except IRI Abort, pressing and holding the abort switch prevents agent release for as long as the switch is held in. For
IRI Abort, the abort switch must be pressed and held before the second alarm activation occurs to prevent release.
Specific operation of the NYC Abort is as follows:
Pressing the Abort switch does the following:
1. Bell and bell strobe turn on (NAC1)
2. Evacuation visuals turn off (NAC3)
3. Evacuation audibles turn off (NAC2)
4. Automatic Release Timer countdown stops at its current value
Releasing the Abort switch starts the 90-second Investigation Timer. When the Investigation Timer expires, the following occurs:
1. Bell and bell strobe turn off (NAC1)
2. Evacuation visuals turn on (NAC3)
3. Evacuation audibles turn on at 120 BPM (NAC2)
4. Reload the Automatic Release Timer with the programmed value
page 46 579-354 Rev. X