EasyManua.ls Logo

Simplex 4004R - Page 41

Simplex 4004R
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 6: Programming the Application Mode
Method Description
Text-Based
Programming
The first prompt, shown below, queries you to select the application mode.
[01] APPLICATION MODE:
d*1 = Agent Release, Single Hazard, Cross Zoned, Combined Release
2 = Agent Release, Single Hazard, Non-Cross Zoned, Combined Release
3 = Agent Release, Dual Hazard, Cross Zone
4 = Agent Release, Dual Hazard, Non-Cross Zoned
5 = Preaction/Deluge, Single Hazard, Cross Zoned, Combined Release
6 = Preaction/Deluge, Single Hazard, Non-Cross Zoned, Combined Release
7 = Preaction/Deluge, Dual Hazard, Cross Zoned
8 = Preaction/Deluge, Dual Hazard, Non-Cross Zoned
9 = Agent Release, Single Hazard, Cross-Zoned, NYC abort
10 = Agent Release and Preaction/Deluge, Single Hazard, Cross-Zoned, Combined
Release
11 = Agent Release and Preaction/Deluge, Single Hazard, Combined Release
12 = Agent Release, Single Hazard, Cross-Zoned, Bell/Horn/Strobe
13 = Agent Release, Single Hazard, Bell/Horn/Strobe
(d=default, *=current setting)
Select Number(X=exit):
Enter the number corresponding to the application mode you want to select and press the carriage return.
Front panel
programming
The top LED (red) on the left side of the display is lit to indicate the application mode is being programmed. The
top LED on the right side of the display is lit to indicate the default application (Agent Release, 1 Hazard, Cross
Zoned, Combined RAC) that is currently selected.
Press ACK to use the default. To choose a different application, do the following:
1. Press the RESET key to move down through the list of available applications. Each time you press this key,
the illuminated LED on the right side of the panel changes to the next one down. If none of the first nine
applications are selected, the second application mode menu will appear. It is shown on the next page.
(Refer to the figure below for the relationship between the LEDs and applications.)
2. When the LED corresponding to the desired application is illuminated, press the ACK key. This saves the
selection in memory and moves you to the next programming step.
page 39 579-354 Rev. X
4004R Fire Alarm installation, programming, and operating instructions