Table 10: Programming the RAC Time Limit Cutout
Method Description
Text-based
programming
The fifth prompt, shown below, asks you to set the RAC Cutout Timer.
[05] RAC TIME LIMIT CUTOUT:
d * 1 = None
2 = 45 sec
3 = 1 min
4 = 3 min
5 = 4 min
6 = 5 min
7 = 6 min
8 = 7 min
9 = 3.5 min
10 = 21 min
11 = 25 min
12 = 34 min
13 = 44 min
14 = 64 min
(d=default, *=current setting) Select Number(X=exit):
Enter the number corresponding to the value you want to select and press the carriage return. Refer to
"Programming Manual Release Time Delay" in the next section for a description of the next programming step.
Front panel
programming
Eight selections are available in this first of two RAC Cutout Time menus – no cutout, 45 seconds, one minute,
three minutes, four minutes, five minutes, six minutes, seven minutes. Use the RESET key to scroll through the
selections. When the desired choice is illuminated, press the ACK key to save the selection in memory and move
to the next programming step. If none of the first eight selections are selected, the second RAC Cutout Time
menu will appear. It is shown on the next page.