- 8 data bits
- 1 stop bit
6. To display the historical log, enter an "L" followed by a carriage return, at the dash prompt.
7. To view the timestamp used by the panel, enter a "T" followed by a carriage return.
To change the timestamp, enter the following command at the dash prompt (where HH is the hour, MM is the minutes, and SS is the
seconds).
T HH:MM:SS
Each field must be separated by a colon.
8. To view the current date set on the panel, enter a "D" followed by a carriage return, at the dash prompt.
To change the date set on the panel, enter the following command at the dash prompt (where MM is the month, DD is the date, and
YY is the year).
D MM/DD/YY
page 56 579-354 Rev. X
4004R Fire Alarm installation, programming, and operating instructions