EasyManua.ls Logo

Simplex 4004R - Page 61

Simplex 4004R
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 20: Initial calculation based on 20 hour rating
20 Hour Rating C/20 (Amps) 20 Hour Rating C/20 (Amps) 20 Hour Rating C/20 (Amps)
4.5 Ah 0.225 12.7 Ah 0.635 55 Ah 2.75
5.0 Ah 0.25 18 Ah 0.90 110 Ah 5.5
If either the Standby Current or the Alarm Current is greater than the C/20 current for the initial battery size selected, a Discharge Factor
(DF) must be applied. For example, 1 A load on a 10 Ah battery requires a Discharge Factor of 1.08 (10 Ah / 1 A gives discharge time of 10
hours; DF = 1.08). Use Table 21 to determine Discharge Factor (use the 20 hr value for 24 hr standby).
Table 21: Determining discharge factor
Discharge Time
Discharge
Factor
Discharge
Time
Discharge
Factor
Discharge
Time
Discharge
Factor
Discharge
Time
Discharge
Factor
0.083 hr 5 min 3.85 2 hr 1.43 8 hr 1.10 14 hr 1.03
0.166 hr 10 min 2.78 3 hr 1.30 9 hr 1.09 16 hr 1.02
0.249 hr 15 min 2.27 4 hr 1.22 10 hr 1.08 18 hr 1.01
0.332 hr 20 min 2.08 5 hr 1.18 11 hr 1.06 20 hr 1.00
0.5 hr 30 min 1.96 6 hr 1.14 12 hr 1.05 48 hr 1.00
1 hr 60 min 1.67 7 hr 1.11 13 hr 1.04 60 hr 1.00
Standby Discharge Factor (SDF) = _________ Alarm Discharge Factor (ADF) = _________
Minimum required battery capacity calculation for a final discharge voltage of 20.4V (to account for battery aging, a 1.17 multiplier is
included). Minimum battery capacity in Ah = 1.17 x [(A x C x SDF) + (0.0167 x B x D x ADF)] = _______
Minimum required battery capacity calculation for a final discharge voltage: 23V.
1.32 × [(A × C × SDF) + (0.0167 × B × D × ADF)] = _______
If the battery size initially selected is smaller than the result of step 9 above, repeat the calculations using a larger battery size.
page 59 579-354 Rev. X
4004R Fire Alarm installation, programming, and operating instructions

Table of Contents

Related product manuals