User Manual
EM100 Mini Inverter
100
No. Function Range Unit Default Type
F11.03
Inverter Rated Power
0.40~22.00
kW XXXX X
F11.04
Inverter Rated Voltage
60~480
V XXX X
F11.05
Inverter Rated Current
0.1~100.0
A XXXXX X
The parameters are only for reference and cannot be edited. Please verify the parameters
with the nameplate before operation.
No. Function Range Unit Default Type
F11.06
Inverter Running Time User Monitoring HOUR XXXXX X
F11.07
Inverter Running Time User Monitoring min XXXXX X
F11.08
Running Time Control
0: Disabled
1: Enabled
0
〇
F11.09
Setting Running Time
0~65535
HOUR 00000
〇
F11.06 Hours that inverter has run. The parameters are only for reference and cannot be
edited. Running time is the time accumulation of operation status.
F11.07 Minutes within 1 hour that inverter has run. The parameters are only for
reference and cannot be edited.
F11.08=0 Running time control disabled.
F11.08=1 Running time control enabled, if the setting operation time is up, inverter trips
InP (Internal fault), and cannot run.
F11.09 For controlling the operation time of inverter.
The permitted operation time = F11.09 -F11.06.
No. Function Range Unit Default Type
F11.10
Distributor Password
0~65535
XXXXX
〇
F11.11
Factory Password
0~65535
XXXXX
〇
In order to prevent the key parameters from being edited and resulting in faults, the
parameters are only for professionals.
No. Function Range Unit Default Type
F11.12
Software Version - XXXXX X
The parameters are only for reference and cannot be edited.