(First) Commissioning SMA Technologie AG
Page 58 SI5048-11:EE4206 Technical Description
5. You are now in the Quick Configuration Guide (QCG).
Here you can select the following:
- "Start System" (if you have accidentally accessed
the QCG and only would like to restart the system)
- "New System" (if you would like to start a new
system or perform changes to the system
configuration)
- "New Battery" (if you would like to change the
main battery settings, but retain the system
configuration)
- "Emerg Charge" (if you would like to charge a
deeply discharged battery using an external source,
see section 19.9 "Troubleshooting" (Page 150))
6. The following parameters must be set when "New System" is selected:
- Voltage/frequency type (230V_50Hz, 220V_60Hz), default is "230V_50Hz"
- System configuration (for this selection, see "System configuration overview:"
(Page 59)), default setting is "1phase 1SI PV"
- Device type (Master, Slave1, Slave2, Slave3)
-Date
-Time
- Battery type (VRLA, FLA, NiCd), default setting is "VRLA"
- Nominal battery capacity (100 to 10000 Ah), default setting is "100 Ah"
- Nominal battery voltage (44 to 48 V), default setting is "48.0 V"
- Maximum generator current (0 to 224 A), default setting is "16 A"
- Generator interface (Manual, GenMan, Autostart), default setting is "Manual"
The following parameters must be set when "New Battery" is selected:
- Battery type (VRLA, FLA, NiCd), default setting is "VRLA"
- Nominal battery capacity (100 to 10000 Ah), default setting is "100 Ah"
- Nominal battery voltage (44 to 48 V), default setting is "48.0 V"
01#StartMenu
New System ↵