SMA Solar Technology AG 7 Commissioning
Installation Manual SI80H-60H-OffGrid-IA-en-11 81
13. Setting the maximum permissible current for an off-grid system with the electricity grid:
Select the 003.21 GdCurNom parameter and
press the button.
Set the maximum permissible current and press the button.
Confirm the maximum current with Y.
14. Setting the maximum generator current for an off-grid system with a generator:
Select the 003.22 GnCurNom parameter and
press the button.
Set the maximum current for permanent loading of the generator and press the button.
Confirm the maximum current with Y.
15. Setting the type of the generator interface for an off-grid system with a generator:
Select the 003.23 GnStrMod parameter and
press the button.
If the generator does not have an electric starting device, set Manual and press the button.
If the generator can be started and stopped using one contact, set Autostart and press the
button.
If the generator is controlled using GenMan, set GenMan and press the button.
Confirm the generator interface with Y.
16. Setting the earthing system of the off-grid system:
Select the 003.24 GndTyp parameter and
press the button.
For a TN system, set TN and confirm the entry.
For a TT system, set TT and confirm.
Confirm the earthing system with Y.