7 Commissioning SMA Solar Technology AG
84 SI80H-60H-OffGrid-IA-en-11 Installation Manual
6. Setting the battery type:
Select the 003.06 BatTyp parameter and
press the button.
If the battery type is FLA, set FLA and press the button.
If the battery type is VRLA, set VRLA and press the button.
Confirm the battery type with Y.
7. Setting the battery voltage:
Select the 003.07 BatVtgLst parameter and
press the button.
Set the battery voltage and press the button.
Confirm the battery voltage with Y.
8. Setting the battery capacity:
Select the 003.09 BatCpyNom parameter
and press the button.
Set the C10 battery capacity and press the button (see Section 7.4.1"Determining the
Battery Capacity",page75).
Confirm the battery capacity with Y.
9. Setting the line voltage and power frequency:
Select the 003.14 AcVtgFrqTyp parameter
and press the button.
For a line voltage of 230 V and 50 Hz, set 230V_50Hz and press the button.
For a line voltage of 220 V and 60 Hz, set 220V_60Hz and press the button.
Confirm the line voltage and power frequency with Y.