SMA Solar Technology AG 7 Commissioning
Installation Manual SI80H-60H-OffGrid-IA-en-11 87
16. Setting the generator interface:
Select the 003.23 GnStrMod parameter and
press the button.
If the generator does not have an electric starting device, set Manual and press the button.
If the generator can be started and stopped using one contact, set Autostart and press the
button.
If the generator is controlled using GenMan, set GenMan and press the button.
Confirm the generator interface with Y.
17. Turn the button to the right.
The Sunny Remote Control shows the last page
of Setup new system.
18. Press the button and confirm the question Done ? with Y.
19. Wait until the inverter LED of slave 1 flashes and the Sunny Remote Control displays
To identify Slave1 press Tss on the Slv.
20. Press the start-stop button on slave 1.
A signal sounds and the QCG configures slave 1.
21. Wait until the inverter LED of slave 2 flashes and the Sunny Remote Control displays
To identify Slave2 press Tss on the Slv.
22. Press the start-stop button on slave 2.
A signal sounds and the QCG configures slave 2.
23. Press the button on the Sunny Remote Control to terminate the QCG.
The off-grid inverter switches to standard mode.
24. Configure the next cluster until all clusters have been configured.