7 Commissioning SMA Solar Technology AG
86 SI80H-60H-OffGrid-IA-en-11 Installation Manual
13. Setting the cluster for an extension cluster:
Select the 003.17 ClstMod parameter and
press the button.
•Set ExtnClst and press the button.
Confirm the extension cluster with Y.
Select the 003.18 ClstAdr parameter and
press the button.
Set the address of the extension clusters and press the button, e.g. set the address of
extension cluster 1 to 1.
Confirm the address of the extension clusters with Y.
Continue with step 16.
14. Setting the type of the Multicluster Box:
Select the 003.19 Box parameter and press
the button.
Set the type of the Multicluster Box and press the button. Tip: The Multicluster Box type is
indicated on the type label of the Multicluster Box.
Confirm the type of the Multicluster Box with Y.
15. Setting the maximum generator current:
Select the 003.22 GnCurNom parameter and
press the button.
Set the maximum current for permanent loading of the generator and press the button.
Confirm the maximum current with Y.