Operating manualSTP110-60-BE-en-1672
12.2.8 Event 010 (Sunny Portal: 1302)
Event message:
Grid power failure
Explanation:
Alternating current switch or alternating current circuit is not connected.
Corrective measures:
Wait until the alternating current switch or alternating current circuit reconnects again. The
inverter is reconnected to the supply grid automatically.
Check whether the supply from the utility grid is normal.
Ensure that the AC cable is correctly connected.
Ensure that the conductors of the AC cables are connected to the correct terminals.
Ensure that AC circuit breaker is connected and switched on.
If the fault cannot be rectified using the indicated corrective measures, contact Service.
12.2.9 Event 011 (Sunny Portal: 6422)
Event message:
Interference device
Explanation:
There is a disturbance in the device.
Corrective measures:
Wait until the inverter is in normal mode again.
Switch off the AC miniature circuit breakers and the DC load-break switches and switch them
on again after 15minutes to restart the inverter.
If the fault cannot be rectified using the indicated corrective measures, contact Service.
12.2.10 Event 012 (Sunny Portal: 3601)
Event message:
Excessive stray current
Explanation:
This fault may be caused by weak solar irradiation or a moist environment.