12 Event messages
SMA Solar Technology AG
Operating manual STP110-60-BE-en-16 73
Corrective measures:
Wait until the ambient conditions improve. The inverter is reconnected to the supply grid.
Ensure that the AC and DC cables are insulated correctly.
If the fault cannot be rectified using the indicated corrective measures, contact Service.
12.2.11 Event 013 (Sunny Portal: 1501)
Event message:
Supply grid fault
Explanation:
The grid voltage or grid frequency is outside the permissible range and the inverter cannot be
connected properly to the supply grid.
Corrective measures:
Wait until the value is within the normal range again. In general, the inverter is reconnected to
the supply grid when the value is back within the normal range.
If the error occurs repeatedly, measure the present grid frequency and contact the local grid
operator concerning solutions if the grid frequency is higher than the set value.
If the fault cannot be rectified using the indicated corrective measures, contact Service.
12.2.12 Event 014 (Sunny Portal: 103)
Event message:
10-minute grid overvoltage
Explanation:
The grid voltage exceeds the preset alternating voltage of the inverter over an extended period of
time.
Corrective measures:
Wait until the value is within the normal range again. In general, the inverter is reconnected to
the supply grid when the value is back within the normal range.
If the fault cannot be rectified using the indicated corrective measures, contact Service.
12.2.13 Event 015 (Sunny Portal: 103)
Event message:
Grid overvoltage