12 Event messages
SMA Solar Technology AG
Operating manualSTP110-60-BE-en-1674
Explanation:
The grid voltage is higher than the set conservation value.
Corrective measures:
Wait until the grid voltage is within the normal range again.
If the error occurs repeatedly, measure the present grid voltage and contact the local grid
operator concerning solutions if the supply grid voltage is higher than the set value.
Ensure that the protection parameters are set correctly.
Ensure that the cross section of the alternating current cable meets the requirements.
If the fault cannot be rectified using the indicated corrective measures, contact Service.
12.2.14 Event 016 (Sunny Portal: not used)
Event message:
Output overload
Explanation:
The configured PV array power is excessively high and is outside the normal operating range of the
inverter.
The inverter interrupts feed-in operation immediately after exceeding a threshold. When the fault is
eliminated, the inverter automatically reconnects to the utility grid.
Corrective measures:
Wait until the value is within the normal range again.
If the fault cannot be rectified using the indicated corrective measures, contact Service.
12.2.15 Event 017 (Sunny Portal: 1416)
Event message:
Unbalanced load of grid voltage
Explanation:
The inverter detects an unbalanced three-phase grid voltage.
Corrective measures:
Wait until the value is within the normal range again.
Measure the current grid voltage. If the grid conductor voltages vary considerably, contact the
grid operator concerning proposals for solutions.
If the voltage difference between the 3 line conductors is within the permissible range of the
local grid operator, change the parameter for the unbalanced load of the grid voltage.
If the fault cannot be rectified using the indicated corrective measures, contact Service.