12 Event messages
SMA Solar Technology AG
Operating manualSTP110-60-BE-en-1676
Corrective measures:
Wait until the inverter is in normal mode again.
Switch off the AC miniature circuit breakers and the DC load-break switches and switch them
on again after 15minutes to restart the inverter.
If the fault cannot be rectified using the indicated corrective measures, contact Service.
12.2.20 Event 024, 025 (Sunny Portal: 6437)
Event message:
Interference device
Corrective measures:
Wait until the inverter is in normal mode again.
Switch off the AC miniature circuit breakers and the DC load-break switches and switch them
on again after 15minutes to restart the inverter.
If the fault cannot be rectified using the indicated corrective measures, contact Service.
12.2.21 Event 030-034 (Sunny Portal: not used)
Event message:
Interference device
Corrective measures:
Wait until the inverter is in normal mode again.
Switch off the AC miniature circuit breakers and the DC load-break switches and switch them
on again after 15minutes to restart the inverter.
If the fault cannot be rectified using the indicated corrective measures, contact Service.
12.2.22 Event 036 (Sunny Portal: 6502)
Event message:
Temperature disturbance
Explanation:
The temperature in the inverter is excessively high and is outside the safe range.
Corrective measures:
Check whether the inverter is exposed to direct sunlight. If so, provide sufficient shading.
Check and clean the air inlets.
Check whether the error message 070 (fan disturbance) is present. If so, replace the fan.