12 Event messages
SMA Solar Technology AG
Operating manual STP110-60-BE-en-16 77
12.2.23 Event 037 (Sunny Portal: 6501)
Event message:
Communication impaired
Explanation:
Error in the communication processor, the inverter continues feeding in, however. The cause must be
determined by the Service.
Corrective measures:
If this message is displayed frequently, contact the Service.
12.2.24 Event 038 (Sunny Portal: 7703)
Event message:
Interference device
Corrective measures:
Wait until the inverter is in normal mode again.
Switch off the AC miniature circuit breakers and the DC load-break switches and switch them
on again after 15minutes to restart the inverter.
If the fault cannot be rectified using the indicated corrective measures, contact Service.
12.2.25 Event 039 (Sunny Portal: 3501)
Event message:
Low system insulation resistance
Explanation:
Generally, the fault is caused by poor insulation of the module/cable to ground or by rainfall and a
moist environment.
Corrective measures:
Check whether the ISO insulation conservation value is excessively high and ensure it complies
with the local requirements.
Check the resistance of the DC string or DC cable to ground. Rectify the fault if a short circuit
or a damaged insulating layer is present.
If the cable shows no abnormalities and the fault occurs on rainy days, check again when the
weather is good.
If the fault cannot be rectified using the indicated corrective measures, contact Service.