Loading...
5 Mounting
SMA Solar Technology AG
Operating manualSTPxx-US-50-BE-en-1130
5 Mounting
5.1 Requirements for Mounting
5.1.1 Requirements for the Mounting Location
WARNING
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires. This can result in death or serious
injury.
Do not mount the product in areas containing highly flammable materials or gases.
Do not mount the product in potentially explosive atmospheres.
A solid support surface must be available. When mounted on drywall or similar materials, the
product emits audible vibrations during operation which could be perceived as annoying.
The mounting location must be suitable for the weight and dimensions of the product.
The installation site can be exposed to direct solar irradiation. There is, however, the possibility
that the product reduces its power output to avoid overheating due to high temperatures.
The mounting location should be freely and safely accessible at all times without the need for
any auxiliary equipment (such as scaffolding or lifting platforms). Non-fulfillment of these
criteria may restrict servicing.
The DC load-break switch of the product must always be freely accessible.
All ambient conditions must be met.
The ambient temperature should be 0°C to +45°C (32°F to +113°F) to ensure optimal
operation.
5.1.2 Permitted and prohibited mounting positions