6 Electrical Connection
SMA Solar Technology AG
Operating manualSTPxx-US-50-BE-en-1136
6 Electrical Connection
6.1 Requirements for the electrical connection
6.1.1 Permitted grid configurations
The inverter approved for operation in the following utility grids:
480V / 277V WYE
6.1.2 Residual-current monitoring unit
The inverter does not require an external residual-current device when operating. If local
regulations require the use of a residual-current device, the following must be observed:
The inverter is compatible with residual-current devices of type A and B that have a rated
residual current of 100mA or higher. Each inverter in the system must be connected to the
utility grid via a separate residual-current device.
6.1.3 Load-break switch and cable protection
In PV systems with multiple inverters, protect each inverter with a separate three-phase circuit
breaker. Make sure to observe the maximum permissible fuse protection (see Section14,
page94). This will prevent residual voltage from being present at the corresponding cable
after disconnection.
Loads installed between the inverter and the circuit breaker must be fused separately.
The load-break switch or circuit breaker must be suitable listed (see National Electrical Code
®
ANSI/NFPA 70) or Canadian Electrical Code
®
CSA C22.1).
The overcurrent protective device for the AC output circuit is to be provided by others.
6.1.4 Requirements on the AC conductors
Conductor type: copper wire
The conductors must be solid or fine-stranded. When using fine-stranded wire, bootlace
ferrules can be used.
Conductor cross-section: 10mm² to 16mm² (8AWG to 6AWG)
Insulation stripping length: 18mm to 20mm (0.71in to 0.79in)
The conductors with regards to its ampacity, rated temperatures, operating conditions and its
power loss must be made in accordance with the local standards and the National Electrical
Code
®
ANSI/NFPA 70 or the Canadian Electrical Code
®
CSA C22.1.