6 Electrical Connection
SMA Solar Technology AG
Operating manual STPxx-US-50-BE-en-11 37
Cable category: minimum CAT5e
Plug type: RJ45 of Cat5, Cat5e or higher
Shielding: SF/UTP, S/UTP, SF/FTP or S/FTP
Number of insulated conductor pairs and insulated conductor cross-section: at least 2 x 2 x
0.22 mm² (2 x 2 x 24 AWG)
Maximum cable length between 2 nodes when using patch cables: 50m (164ft)
Maximum cable length between 2 nodes when using installation cables: 100m (328ft)
UV-resistant for outdoor use.
6.1.6 Requirements for the PV modules per input
All PV modules should be of the same type.
All PV modules should be aligned and tilted identically.
The maximum permitted system voltages of the inverter must not be exceeded.
The maximum short-circuit current must not be exceeded.
The positive connection cables of the PV modules must be equipped with positive DC
connectors.
The negative connection cables of the PV modules must be equipped with the negative DC
connectors.
6.1.7 Requirements on the equipment grounding conductor of
the PV modules
The conductors must be made of solid wire, stranded wire or fine stranded wire. When using
fine stranded wire, bootlace ferrules must be used.
Conductor type: aluminum and copper wire
Conductor cross section: 2.5mm² to 25mm² (14AWG to 4AWG)
6.1.8 DC cable requirements
Conductor cross-section: 3.31mm² to 5.26mm² (12AWG to 10AWG)
Conductor type: copper wire
Maximum permissible temperature: 90°C (194°F)
The conductors with regards to its ampacity, rated temperatures, operating conditions and its
power loss must be made in accordance with the local standards and the National Electrical
Code
®
ANSI/NFPA 70 or the Canadian Electrical Code
®
CSA C22.1.
6.1.9 Signal cable requirements
The cable length and quality affect the quality of the signal. Observe the following cable
requirements:
Conductor cross-section: 0.5mm² to 0.75mm² (21AWG to 19AWG)
External diameter: Max. 8mm (0.3in)
Maximum cable length: 100m (328ft)
Insulation stripping length: 6mm (0.24in)