14 Technical Data
SMA Solar Technology AG
Operating manualSTPxx-US-50-BE-en-1196
STP 20-US-50 STP 25-US-50 STP 30-US-50
Maximum apparent
power
20000VA 25000VA 30000VA
Rated apparent power 20000VA 25000VA 30000VA
Nominal grid voltage 480 V / 277 V 480 V / 277 V 480 V / 277 V
Rated grid voltage 277V 277V 277V
Voltage range
2)
244V to 305V 244V to 305V 244V to 305V
Rated current at 277V 24A 30A 36A
Maximum output cur-
rent
24A 30A 36A
Maximum output cur-
rent under fault condi-
tions
682.5 Apeak / 10 ms 682.5 Apeak / 10 ms 682.5 Apeak / 10 ms
Total harmonic distor-
tion of the output cur-
rent with total harmonic
distortion of the AC
voltage <2%, and AC
power >50% of the
rated power
< 3% < 3% < 3%
Inrush current <10% of the nominal
AC current for a
maximum of 10ms
<10% of the nominal
AC current for a
maximum of 10ms
<10% of the nominal
AC current for a
maximum of 10ms
Rated grid frequency 60Hz 60Hz 60Hz
Grid frequency
2)
60 Hz 60 Hz 60 Hz
Operating range at
grid frequency 60Hz
50Hz to 66Hz 50Hz to 66Hz 50Hz to 66Hz
Power factor at rated
power
1 1 1
Displacement power
factor, adjustable
0.8overexcitedto0.8
underexcited
0.8overexcitedto0.8
underexcited
0.8overexcitedto0.8
underexcited
Feed-in phases 3 3 3
Connection phases 3-(N)-PE 3-(N)-PE 3-(N)-PE
Overvoltage category
in accordance with
UL62109-1
III III III
2)
Depending on the configured country data set