APC615 Pump Unit Controller User Manual
APC615 Pump Unit Controller Version 1.0 2017-10-20 Page 23 of 54
No.
Items
Parameter
Default
Description
CAUTION: Factory default password is
00318, operator can change the password to
avoid nonprofessionals modification. Please keep
in mind of the new password, if forget, please
contact with factory service personnel.
5
Time and Date
Users can calibrate date and time.
Scheduler And Maintenance
1
Scheduled Run
(0-1)
0
0: Disable1: Enable
2
Scheduled Not Run
(0-1)
0
0: Disable1: Enable
3
Maintenance 1
(0-1)
0
0: Disable1: Enable
Users can set maintenance time, maintenance
due action, time and action of pre-alarm A and
pre-alarm B, timer mode and reset
maintenance alarm. If maintenance due alarm
occurs, users can reset maintenance alarm to
remove it.
Details please to see Table 15.
4
Maintenance 2
(0-1)
0
5
Maintenance 3
(0-1)
0
6
Maintenance 4
(0-1)
0
7
Maintenance 5
(0-1)
0
Analog Sensors
Temperature Sensor
1
Curve Type
(0-15)
9
SGD. See table12.
2
Open Circuit Action
(0-2)
0
0: Warning; 1: Shutdown; 2: No action
3
Display Unit
(0-1)
0
0:℃ 1:℉
4
High Temp.
Shutdown
(0~300)ºC
98
Shutdown when external sensor temperature
is higher than this value. Detecting only after
safety delay is over. The delay value can be
set.
5
High Temp.
Warning
(0~300)ºC
95
Warning when external sensor temperature is
higher than this value. Detecting only after
safety delay is over. The delay value and
return value can be set.
6
Low Temp.
Warning
(0-300)ºC
70
Warning when external sensor temperature is
lower than this value. Detecting only after
safety delay is over. The delay value and
return value can be set.
7
Heater Control
((-50)-300)ºC
50
Heater control outputs when external sensor
temperature is lower than this value. The delay
value and return value can be set.
8
Cooler Control
((-50)-300)ºC
80
Heater control outputs when external sensor
temperature is higher than this value. The
delay value and return value can be set.
9
Custom Curve
Users should set the corresponding curve
when select resistor curve type or current
curve type.
Fuel Level Sensor

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Smartgen APC615 and is the answer not in the manual?