UPS/NTA GB/DMX-DMP JBUS.D Page 12 / 22
6. MEASUREMENTS: Address 0x1060, up to 48 words
Code Description Unit ADDRESSES REMARKS
M00 Load rate phase1 % 0x1060
M01 Load rate phase 2 % 0x1061 Set to 0xFFFF if one phase
M02 Load rate phase 3 % 0x1062 Set to 0xFFFF if one phase
M03 UPS load rate % 0x1063
M04 Battery Capacity % 0x1064
M05 Battery Capacity Ah*10 0x1065
M06 Input bypass voltage phase 1 V 0x1066
M07 Input bypass voltage phase 2 V 0x1067 Set to 0xFFFF if one phase
M08 Input bypass voltage phase 3 V 0x1068 Set to 0xFFFF if one phase
M09 Output voltage phase 1 V 0x1069
M10 Output voltage phase 2 V 0x106A Set to 0xFFFF if one phase
M11 Output voltage phase 3 V 0x106B Set to 0xFFFF if one phase
M12 0x106C Set to 0xFFFF (-1)
M13 0x106D Set to 0xFFFF (-1)
M14 0x106E Set to 0xFFFF (-1)
M15 Output current phase 1 A*10 0x106F
M16 Output current phase 2 A*10 0x1070 Set to 0xFFFF if one phase
M17 Output current phase 3 A*10 0x1071 Set to 0xFFFF if one phase
M18 Input bypass frequency Hz*10 0x1072
M19 Output frequency Hz*10 0x1073
M20 Battery voltage (+) V*10 0x1074
M21 Battery voltage (-) V*10 0x1075 Set to 0
M22 Ambient Temperature °C 0x1076
M23 Remaining backup time Minutes 0x1077 Set when the load is on
battery
M24 Battery current A*10 0x1078
M25 0x1079 Set to 0xFFFF (-1)
M26 0x107A Set to 0xFFFF (-1)
M27 0x107B Set to 0xFFFF (-1)
M28 Rectifier voltage (+) V 0x107C
M29 Rectifier voltage (-) V 0x107D Set to 0
M30 0x107E Set to 0xFFFF (-1)
M31 0x107F Set to 0xFFFF (-1)
M32 0x1080 Set to 0xFFFF (-1)
M33 Rectifier input voltage phase 1 V 0x1081
M34 Rectifier input voltage phase 2 V 0x1082
M35 Rectifier input voltage phase 3 V 0x1083
M36 UPS output power kW*10 0x1084
M37 Output power phase 1 kVA*10 0x1085
M38 Output power phase 2 kVA*10 0x1086 Set to 0xFFFF if one phase
M39 Output power phase 3 kVA*10 0x1087 Set to 0xFFFF if one phase
M40 0x1088 Set to 0xFFFF (-1)
M41 0x1089 Set to 0xFFFF (-1)
M42 0x108A Set to 0xFFFF (-1)
M43 0x108B
M44 0x108C
M45 0x108D
M46 0x108E
M47 0x108F