UPS/NTA GB/DMX-DMP JBUS.D Page 8 / 22
1. UPS IDENTIFICATION: Address 0x1000, 12 words
CODE DESCRIPTION
Number of
WORDS
ADDRESS Type Remarks
I00 UPS CODE 1 WORD 0x1000 Numeric value 515 = DELPHYS MX
516 = DELPHYS MX elite
I01 UPS Power 1 WORD 0x1001 Numeric value In kVA * 10
5000 = 500kVA
I02 Module
number
1 WORD 0x1002 Numeric value 1
I03 Serial
number
5 WORDS 0x1003 1 word = 2 ASCII
codes
LSB = 1. char
MSB = 2. char
UPS Code:CCCCCCAaYYYXXXXXXNNn
Code read :aXXXXXXXXn
I04 Reserved 1 WORD 0x1008 0
I05 Reserved 1 WORD 0x1009 0
I06 Reserved 1 WORD 0x100A 0
I07 Reserved 1 WORD 0x100B 0
2. DATE & HOURS: Address 0x1360, 4 words
CODE DESCRIPTION
Number of
words
Addresses Type Remarks
D00 Minutes /
seconds
1 0x1360 Byte value MSB = minutes
LSB = seconds
D01 Hours / day 1 0x1361 Byte value MSB = day
LSB = hours
D02 Month / day
of
week
1 0x1362 Byte value MSB = month
LSB = day of the week
1=Monday
7=Sunday
D03 year 1 0x1363 00 = 2000
3. UPS CONFIGURATION: Address 0x10E0, 32 words
Code Measurements Unit Address REMARKS
T00 Nominal start input voltage V 0x10E0
T01 Nominal start output
voltage
V 0x10E1
T02 Nominal input frequency Hz 0x10E2
T03 Nominal output frequency Hz 0x10E3
T04 Version value * 100 0x10E4 100 = V1.00
T05 0x10E5
T06 0x10E6
TO7 0x10E7
T08 Nominal battery capacity Ah * 10 0x10E8 3000 = 300Ah
T09 Number of battery elements 0x10E9
T10 Reserved 0x10EA Set to 0xFFFF (-1)
T11 Reserved 0x10EB Set to 0xFFFF (-1)
T12 Reserved 0x10EC
T13 Working mode Bits field
0x10ED b0 not used
b1 = with battery
b2 = Gen Set present
b3 = ’energy saver’ enabled
T14 Redundancy level (only in
//)
value 0x10EE 0 = without
1 = N+1
T15 Reserved 0x10EF 100
T16
..
T31
Reserved
0x10F0
0x10FF
Set to 0xFFFF (-1)