UPS/NTA GB/DMX-DMP JBUS.D Page 22 / 22
ANNEX: SPECIFIC JBUS/MODBUS TABLES
For specific needs
To optimize the data traffic between the UPS and the remote equipment, DELPHYS MX / MP is able to
sent in one frame all information, including states and alarms, and also measurements.
The addressing map is absolute; this means that the first address defines the complete table. The next
address defines an other data table.
To use this specific mapping, you need to check if your remote system is able to manage the address
mapping independently of the length of it.
Specific JBUS/MODBUS Tables
TABLE
Absolute address length Function
Common UPS DATA
0x0387 11 (176 bits) 3 READ
Common Measurements
0x0397 64 3 READ
DATA unit 1
0x0381 11 3 READ
Measurements unit 1
0x0391 64 3 READ
DATA unit 2
0x0382 11 3 READ
Measurements unit 2
0x0392 64 3 READ
DATA unit 3
0x0383 11 3 READ
Measurements unit 3
0x0393 64 3 READ
DATA unit 4
0x0384 11 3 READ
Measurements unit 4
0x0394 64 3 READ
DATA unit 5
0x0385 11 3 READ
Measurements unit 5
0x0395 64 3 READ
DATA unit 6
0x0386 11 3 READ
Measurements unit 6
0x0396 64 3 READ
DATA fields detail
The data list and measurements are available on request, please contact the factory.