UPS/NTA GB/DMX-DMP JBUS.D Page 20 / 22
6. MEASUREMENTS: Address 0x60, 48 words
Code Measurements Units
ADDRESS
LSB byte
REMARKS
MO0 Load rate phase1 % 0x60
M01 Load rate phase 2 % 0x61 Set to 0xFFFF if one phase
M02 Load rate phase 3 % 0x62 Set to 0xFFFF if one phase
M03 UPS load rate % 0x63
M04 Battery Capacity % 0x64
M05 Battery Capacity Ah*10 0x65
M06 Input bypass voltage phase 1 V 0x66
M07 Input bypass voltage phase 2 V 0x67 Set to 0xFFFF if one phase
M08 Input bypass voltage phase 3 V 0x68 Set to 0xFFFF if one phase
M09 Output voltage phase 1 V 0x69
M10 Output voltage phase 2 V 0x6A Set to 0xFFFF if one phase
M11 Output voltage phase 3 V 0x6B Set to 0xFFFF if one phase
M12 0x6C Set to 0xFFFF (-1)
M13 0x6D Set to 0xFFFF (-1)
M14 0x6E Set to 0xFFFF (-1)
M15 Output current phase 1 A*10 0x6F
M16 Output current phase 2 A*10 0x70 Set to 0xFFFF if one phase
M17 Output current phase 3 A*10 0x71 Set to 0xFFFF if one phase
M18 Input bypass frequency Hz*10 0x72
M19 Output frequency Hz*10 0x73
M20 Battery voltage (+) V*10 0x74
M21 Battery voltage (-) V*10 0x75 Set to 0
M22 Ambient Temperature °C 0x76
M23 Remaining backup time Minutes 0x77 Set when the load is on battery
M24 Battery current A*10 0x78
M25 0x79 Set to 0xFFFF (-1)
M26 0x7A Set to 0xFFFF (-1)
M27 0x7B Set to 0xFFFF (-1)
M28 Rectifier voltage (+) V 0x7C
M29 Rectifier voltage (-) V 0x7D Set to 0
M30 V 0x7E Set to 0xFFFF (-1)
M31 V 0x7F Set to 0xFFFF (-1)
M32 0x80 Set to 0xFFFF (-1)
M33 Rectifier input voltage phase 1 V 0x81
M34 Rectifier input voltage phase 2 V 0x82
M35 Rectifier input voltage phase 3 V 0x83
M36 UPS output power kW*10 0x84
M37 Output power phase 1 kVA*10 0x85
M38 Output power phase 2 kVA*10 0x86 Set to 0xFFFF if one phase
M39 Output power phase 3 kVA*10 0x87 Set to 0xFFFF if one phase
M40 0x88 Set to 0xFFFF (-1)
M41 0x89 Set to 0xFFFF (-1)
M42 0x8A Set to 0xFFFF (-1)
M43 0x8B
M44 0x8C
M45 0x8D
M46 0x8E
M47 0x8F
Rectifier and battery measurements are not available in the ‘CC’ table (common bypass)