socomec DELPHYS MX - Control Functions for Parallel Systems; Enabled Controls by Module; Sending Controls to UPS (Module Specific)

socomec DELPHYS MX
23 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS/NTA GB/DMX-DMP JBUS.D Page 21 / 22
7. ENABLED CONTROLS TABLE: Address 0x15C0, 2 words
CODE DESCRIPTION BIT ADDRESS REMARKS
C00 0
C01 1
C02 2
C03 Eco-mode enabled 3 0x15C0
C04 Mode normal enabled 4 0x15C0
C05 5
C06 6
C07 7
C08 8
C09 9
C10 Automatic Bypass transfer enabled 10 0x15C0
C11 Inverter transfer enabled 11 0x15C0
C12 12
C13 13
C14 14
C15 15
C16 Battery test enabled module 1 0 0x25C1
C16 Battery test enabled module 2 0 0x35C1
C16 Battery test enabled module 3 0 0x45C1
C16 Battery test enabled module 4 0 0x55C1
C16 Battery test enabled module 5 0 0x65C1
C16 Battery test enabled module 5 0 0x75C1
Remark: A bit set to 0 means that the control is disabled by the UPS. The control will be not executed.
8. TO SEND CONTROL TO UPS: Address 0x15B0, write 1 words
For a remote UPS control, it is necessary to set the serial interface in “remote” mode using the Human
Machine Interface.
Local controls of the control panel or graphic touch screen are no more available.
The control table below shows if the selected control is allowed or not. If the control sent to the UPS is not
allowed, the function will be ignored.
Controls available by JBUS/MODBUS connection:
Code Control Value to write ADDRESS REMARKS
C03 Eco-mode 0x0003 0x15B0
C04 Normal mode 0x0004 0x15B0
C10 Automatic bypass transfer 0x000A 0x15B0
C11 Inverter transfer 0x000B 0x15B0
C16 Battery Test module 1 0x0010 0x25B0
C16 Battery Test module 2 0x0010 0x35B0
C16 Battery Test module 3 0x0010 0x45B0
C16 Battery Test module 4 0x0010 0x55B0
C16 Battery Test module 5 0x0010 0x65B0
C16 battery Test module 6 0x0010 0x75B0