30
Wait
Testing 81>S1...
Wait
Test 81>S1 OK!
Wait
Testing 81>S2
Wait
Test 81>S2 OK!
Wait
Testing 81<S1...
Wait
Test 81<S1 OK!
Wait
Testing 81<S2...
Wait
Test 81<S2 OK!
Press Ok
Auto Test OK!
Press Down
59.S1 threshold 253V 900ms
Press Down
59.S1: 228V 902ms
Press Down
59.S2 threshold 264.5V 200ms
Press Down
59.S2: 229V 204ms
Press Down
27.S1 threshold 195.5V 400ms
Press Down
27.S1: 228V 408ms
Press Down
27.S2 threshold 92V 200ms
Press Down
27.S2: 227V 205ms
Press Down
81>.S1 threshold 50.5Hz 100ms
Press Down
81>.S1 49.9Hz 103ms
Press Down
81>.S2 threshold 51.5Hz 100ms
Press Down
81>.S2 49.9Hz 107ms
Press Down
81<.S1 threshold 49.5Hz 100ms
Press Down
81<.S1 50.0Hz 105ms
Press Down
81<.S2 threshold 47.5Hz 100ms
Press Down
81<.S2 50.1Hz 107ms