NOTE
Utility interconnection may require approval from the authority having
jurisdiction.
Approval from the authority having jurisdiction is required for making
adjustments to utility interactive setpoints.
NOTE
Solaredge inverters always opens a disconnecting means when the inverter
ceases to deliver power as a result of abnormal voltage or frequency conditions
or in response to a detected unintentional island.
NOTE
The current unbalance shall be defined as the maximum deviation of line
current on any phase, from the average line current of all phases, expressed as a
percentage.
The measured maximum inverter current unbalance is as specified in the below
table:
Model
% Current unbalance
phase A
% Current unbalance
phase B
% Current unbalance
phase C
SE43.2K 2.0082 0.0171 1.9908
SE50K 1.7511 0.0978 1.8489
SE66.6K 1.3706 0.0966 1.274
SE80K 1.2938 0.0596 1.2342
SE100K 2.0559 0.1449 1.911
SE110K 1.9407 0.0894 1.8513
SE120K 1.9407 0.0894 1.8513
WARNING!
SolarEdge products can expose you to chemicals including antimony trioxide,
which is known to the State of California to cause cancer. For more information,
go to www.P65Warnings.ca.gov .
AVERTISSEMENT!
Les produits SolarEdge peut vous exposer à des agents chimiques, y compris
trioxyde d'antimoine, identifiés par l'État de Californie comme pouvant causer
le cancer. Pour de plus amples informations, prière de consulter
www.P65Warnings.ca.gov.