32
Connect RS485 male terminal with its female terminal, Tighten the locking caps to a
torque of 8 N·m as well as waterproof cable connectors.
Step 5
To prevent corrosion apply silica gel or fireproof mud to the terminal,
or interface after connecting external PGND cables AC cables, ,
RS485 port and Ethernet port, .
NOTE
5 4 3 Setting RS485 Communication Address. .
Step 1 Input the companys website in your mobile phone browser and click APP to
Download mobile APP which is also available by scanning the QR code And then login the, .
APP and register an account for your inverter.
Step 2 Click the Extension key and select Setting in the prompt manual as shown in Figure 5 20, , . .
Figure 5 20 APP homepage setting.
SEBLE-SE
History
Generating capacity
Maintenance
Setting
Standby Mode
Step 3 Check the Modbus address in Figure 5 21 the default address is 1 long click to revise. , ,
the address and save it the inverter at same RS485 bus must be set a unique address, .
Figure 5 21 Check the Modbus address.
Setting
Basic Setting
Date and time
2018-01-21 12:14:25
IP address
0.0.0.0
ModBus
Address:1
Protocol: ModBus RTU
Baud Rate: 9600