6.5.16 Compensation Set
The screen shows:
Figure 6.47 Power Rate Limit
YES=<ENT> NO=<ESC>
Power para:1.000
Press the Down key to move the cursor.
Press the Up key to change the digit.
Please press the Enter to save the setting and press the ESC key to return to the previous
menu.
This setting is used for grid operators, do not change this setting unless
specifically instructed to.
This function is used to calibrate inverter output energy and voltage. It will not impact the
energy count for inverter with RGM.
Two sections are included: Power Parameter and Voltage Parameter.
6.6 Arc fault (AFCI version)
Solis single phase inverters have a built-in AFCI function which can detect an arc fault
within the DC circuit. If the arc fault happens, it can only be removed manually.
During normal operation, if arc fault happens in the DC circuit, the inverter will stop
output and the LCD will show:
Figure 6.48 Arc Fault
ARC-FAULT
Restart Press ESC 3s
Please check DC cables and connections to identify the source of possible arcing. Then
press <ESC> for 3 seconds, the inverter will restart.
6. Operation
User Manual
49