39 © STULZ GmbH – all rights reserved EN/09.2017/G44
cybercool indoor chiller original instructions
NOTICE
A too high pre-filling can cause that liquid refrigerant gets in the compressor and the compres-
sor is damaged.
A too low pre-filling leads to the triggering of the LP switch and shut-down of the compressor.
• Continue the lling while the compressor is running.
• Stop the lling once you see only small bubbles in the sight glass.
• Note the weight of the refrigerant bottle and determine the quantity of charged refrigerant.