cybercool indoor chiller original instructions
© STULZ GmbH – all rights reserved EN/09.2017/G44
Refrigerant charge - Quantity and Purity
Quantity
An unsufficient charge causes the formation of bubbles in the sight glass or in extreme cases the triggering of

of cooling capacity and to high superheating temperatures, which have a disadvantageous effect on the com-
pressor lifetime.
If a leak is detected:
 

rel
.
 
 
 
 
 
evacuate the refrigerant circuit resp. the closed off section by a vacuum pump.
 
An overfilling of the circuit makes the condensation pressure rise and by that the power consumption of the

After repairing a leak, check the refrigeration circuit on tightness within one month.






Purity
Bubbles in the sight glass indicate that the charge is unsufficient or that the filter drier is clogged.
A pollution of the filter drier, whose origin task is to clear the refrigerant from impurities and humidity, can be
detected by a temperature difference upstream and downstream the filter drier.


7.3 Refrigerant circuit