SUMAVISION EMR Operation Introduction
10 /53
the door or routine maintenance. The cabinet can not be installed against the wall, and the
distance between the cabinet side and the wall should be not less than 0.8m.
Site room floor:
Site room floor should be non-conductive, dust-proof, and its surface smoothness error
should be less than 2mm per square meter. The volume resistivity of anti-static material
should range from 10
7
Ω to 1×10
20
Ω, and the ground current-limiting resistor is 1MΩ.
Floor load-bearing should be larger than 450kg/ m
2
.
Environment temperature:
The device can operate normally in the environment whose temperature ranges from 10
to 40, and the places where conditions permit can install air-conditioning system for
cooling.
Relative humidity:
Normal working humidity: ≤90% (20);
Allowed working humidity: ≤95% (without condensation).
Environmental pressure:
86-105kpa.
Site room doors and windows:
Doors and windows of the site room should be sealed with dust-proof rubber strips, and
windows should be double-glazed and strictly sealed.
Site room wall suface:
The wall suface of site room can use wallpapers or be printed with lusterless paint,
however, powder coating is not suitable.
Air cleanliness:
The requirements are shown as Table 3-2 Site room dust indicators and Table 3-3
Table 3-2 Site room dust indicators
Maximum diameter (μm)
0.05
1.00
3.00
5.00
Maximum concentration (particles per cubic meter)
14×10
5
10
5
24×10
4
13×10
4
Table 3-3 Site room harmful gas indicators.
Gas
Average (mg/m
3
)
Max. (mg/m
3
)
Sulfur dioxide SO
2
0.20
1.50
Hydrogen sulfide, H
2
S
0.01
0.30
Nitrogen dioxide, NO
2
0.04
0.15
Ammonia, NH
3
0.05
0.15
Chlorine, Cl
2
0.01
0.30
Fire-fighting requirements:
Site room should be equipped with automatic fire alarm system, hand-held extinguishing

Table of Contents