After few minutes the following message will be displayed:
Open the red bottle valve, then press OK:
After few minutes the following message will be displayed:
BOTTLE PRESSURE calibration successfully completed, Press OK return exit.
Switch off the machine and disconnect it from the electrical supply.
R134a BOTTLE PRESSURE
PB
AUTOMATIC CALIBRATION
Calibration running
Please wait…
PB AUTOMATIC CALIBRATION
R134a BOTTLE PRESSURE
PB
AUTOMATIC CALIBRATION
Open the red bottle valve
Press OK
R134a BOTTLE PRESSURE
PB
AUTOMATIC CALIBRATION
Calibration running
Please wait…
PB AUTOMATIC CALIBRATION
R134a BOTTLE PRESSURE
End of
PB
AUTOMATIC CALIBRATION
Press OK