15
The ambient temperature and relative humidity must meet the following
requirements.
Do not install the inverter outdoors in areas with salt damage, which mainly refer to
the areas within 500 m away from the coast. The deposition of salt fog varies largely
with nearby seawater characteristics, sea wind, precipitation, relative humidity,
terrain, and forest coverage.
Prevent the inverter from direct exposure to sun, rain and snow.
The inverter should be well ventilated. Ensure air circulation.
Never install the inverter in living areas. The inverter will generate noise during
operation, affecting daily life.
4.2.2 Carrier Requirements
The installation carrier should meet the following requirements:
4.2.3 Installation Angle Requirements
Inverter vertically or at a minimum back tilt of 10°. Forward installation or upside down
installation is prohibited.
User Manual 4 Mechanical Mounting