© Copyright Mission Critical Energy Inc, 2019 Version 1-2019
www.superwind.com
Check the battery electrolyte levels (where applicable) and add distilled water as
necessary. Refer to the maintenance instructions provided by the battery
manufacturer for specific instructions.
10.2 Maintenance
Your Superwind 350/48V requires no special maintenance, however the above
inspections should be performed annually unless events dictate that additional
inspections should be conducted.
Most issues that occur after installation of your new Superwind 350/48V can be resolved by
following the below trouble shooting guide.
Use caution and remain aware of electrical and mechanical hazards at all times:
Never approach a turning rotor.
Never attempt to stop the rotor by hand.
Exercise extreme caution when working on the electrical
system as most of the lines are energized.
Never short-circuit the batteries.
The following tools will be useful for troubleshooting:
A multi-meter (for checking voltage, current and resistance).
An anemometer (for checking wind speed).
11.1 Wind generator does not start
Wait for more wind
Note: Start-up wind speed is
3.5 m/s [11.5 ft/s - 7.8 m/h]
(slightly higher during break-in
period)
Stop switch in STOP
position
Observe stop switch position
Place stop switch to RUN
position
Stop switch wired
incorrectly
Check stop switch connections
Wire stop switch correctly