12.2Set‐upforDanfossFC101forDV‐unitswithACmotors
SETUPISDONEINFACTORYBEFOREDELIVERY
ToreloadSystemairfactorysettingsfromthecontrolpanel:
0‐50:LCPCopy: [2]
Systemairfactoryset ‐upisbasedonDanfossinitialization.
14‐22:Operationmode: [2]Initialisation(DanfossInitialisation)
Turnpoweroffandon.
Systemairfactoryset‐up:
0‐01:Languageselection:
1‐03:Torquecharacteristic: Singlefan:[3]Auto‐Energyoptim.
Withtwinfanset‐up:[1]VariableTorque
1‐20:MotorPower: Accordingtomotorplate/orderpapers
Withtwinfanset‐uptotalpowermustbeused
1‐24:MotorCurrent: Accordingtomotorplate
/orderpapers
Withtwinfanset‐uptotalcurrentmustbeused
1‐25:MotorNominalSpeed:Accordingtomotorplate/orderpapers
1‐42:MotorCableLength: 3m
1‐50:MotorMagnetisationatzerospeed.: 0%
1‐52:Min.SpeedNormalMagnetisation: 10Hz
1‐73:
FlyingStart: [1]Enable
1‐90:MotorThermalProtection: [2]Thermistortrip
3‐15:Reference1Source: [2]AnaloginputAI54
1‐93:ThermistorSource: [1]AnaloginputAI53
3‐03:MaximumReference: Max.Hzfromorderpapers
3‐16+3‐17:Reference2‐and3Source: [0]Nofunction
3‐41:Ramp1up: 60Sec.
3‐42:Ramp1down: 30Sec.
4‐19:Max.OutputFrequency: 90Hz
4‐14:MotorSpeedHighLimit: 90Hz
5‐12:Terminal27Digitalinput: [0]Nooperation
5‐40.0:FunctionRelay: [3]Driveready/remote
5‐40.1:FunctionRelay: [3]Driveready/remote
6‐25:Terminal54HighReference: Max.Hzfromorderpapers
14‐20:ResetMode: [2]Automaticresetx2
0‐50:LCPCopy: [1]AlltoLCP(CopyofSystemairfactorysettingstopanel)
Connections:
0‐10V: terminal54‐55
Start: terminal12‐18
Thermistor: terminal50‐53
Driveready: terminal1‐2
